3690 NW 53rd Street • Fort Lauderdale, FL 33309 • Ph 954-739-4300 • Fax 954-486-4968 • www.dynalco.comDYNALCOSW-100Speed Switch / TransmitterOperati
1 zzSimple on-line trip frequency setting (using actualinput signal or frequency generator)zzUser settable trip frquency from 0.1 Hz t
SPECIFICATIONS (Cont’d)5. CONTROL INPUTS: Active low (VIL= 0.5 V max.) internally pulled up to 5VDC through a 100 KΩ resistor (ISNK= 50 μA). Response
3OVERVIEWThe SW-100 continuously monitors the input signal and controls an outputrelay based on the frequency of the input signal, the chosen Operatio
4CONNECTIONS & CONFIGURATION SWITCH SET-UP FOR VARIOUS SENSOR OUTPUTS Note: Separate power supplies must be used for sensor power and input power
1.1 Place DIP switch 4 to the ON (up) position and DIP switches 5, 6, and 7 as shown.1.2 Green input LED blinks the setting corresponding to the Opera
63.1 Place DIP switch 4 to the ON position and DIP switches 5, 6, and 7 as shown.3.2 The Green input LED blinks the existing Trip Frequency setting, p
7For Overspeed operation, the Relay Trip point is internally set to the Trip Frequency plus theOffset value. For Underspeed operation, the Relay Trip
INSTALLATIONThe unit is equipped with a universal mounting foot for attachment tostandard DIN style mounting rails, including G profile rail according