Dynalco SWT-2000 Speed Switch/Speed Transmitter Manual do Utilizador Página 7

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 35
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 6
Operating Instructions SWT-2000 DYNALCO
3
Input signal for fixed 3V
trigger (+/-15%)
Max. Voltage: 80V
RMS
(226V
pp
)
Best suited to digital signals
Schmitt Trigger Input (Hysteresis > 1V)
„0“ = Low Level to 1.25V
„1“ = High level from 3V (+/- 15%)
Min. Pulse width: 5μs
NO DC- decoupling
Input signal for adaptive
trigger min. 57mVpp
(+/-10%) 20mV
RMS
Max. Voltage: 80V
RMS
(226V
pp
)
DC- decoupling
The Trigger level automatically adapts itself to the input signal in the range
+28.5mV to +2V. The Adaptive Trigger improves the signal to noise immunity
e.g. where electromagnetic sensors are used.
Min. Trigger level: 57 mVpp +/-10% = 20 mV
RMS
+/-10% U min. = f(Frequency)
0.01
0.10
1.00
10.00
100.00
1000.00
0.01
0.1
1
10
100
1000
10000
100000
Frequency (Hz)
Sensor Signal (Vpp)
O.K
NOT O.K.